Flicker severity
The 3 supply phases are checked. The method used to calculate the flicker is an
approximation of the standard method. Default Value: limit x10
Voltage dips
The 3 supply phases are checked. Voltage drops below 90% of the nominal supply voltage
and less than 1 minute in duration are detected.
A waveform is stored for this event. Default Value: 90%
Voltage interruptions
The 3 supply phases are checked. Voltage drops below 10% of the nominal supply voltage
and less than 3 minutes in duration are detected.
A waveform is stored for this event.
Temporary overvoltage
The 3 supply phases are checked. Overvoltage above 110% of the nominal supply voltage
and less than 3 minutes in duration are detected.
A waveform is stored for this event. Default Value: 110%
Transient overvoltage
The 3 supply phases are checked. Overvoltage above 150% of the nominal supply voltage
and less than 1 minute in duration are detected.
A waveform is stored for this event. Default Value: 150%
Voltage unbalance
The 3 supply phases are checked. Unbalance above 2% is detected.
A waveform is stored for this event. Default Value: 2%
Harmonic voltage
The 3 supply phases are checked. Total harmonic distortions of a voltage above 8% are
detected. Harmonics are detected up to the 15th harmonic.
A waveform is stored for this event. Default Value: 8%
.
Current limit
The 3 supply phases are checked. Currents above maximum current range are detected.
A waveform is stored for this event. Default Value: 3000Arms