Custom Sensors CCD8000 Manuel de service Page 15

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 49
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 14
Safety Instructions and Warranty Terms 12
Manual econ sens+ Version 1.40
RS485-Interface
The econ sens + supported on this interface the following protocols:
Modbus RTU
Modbus RTU
Via the RS485 Modbus RTU protocol, the values "Modbus / pulses / s submenu " p.17 ff) can be
retrieved according to section.
To use Modbus RTU a Modbus master is required. In a segment of up to 32 devices can be connected
together. For more than 32 devices in a segment repeaters are required. The wiring of components is
a “linear structure”, as shown in Fig 13. Other bus topologies, such as Star shape is not possible.
At the beginning and end of a segment, the cable is terminated with resistors (bus termination). Put
between lines A and B a 120 Ω termination resistor. As a connecting line between the devices we
recommend a shielded cable 2x2x0, 8, for example, Belden YE00820 or a Cat 5 network cable. The
maximum length is 1200 meters.
Figure 13: Assignment of the RS485 outputs (here with one econ sens+ as gateway)
Vue de la page 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 48 49

Commentaires sur ces manuels

Pas de commentaire